Tiếng Việt   English

AC Current / Voltage Transducer (1P)

AC Current / Voltage Transducer (1P)

 

FEATURES

 RatingcurrentAC5A, range: AC0~7.5A
 Dualaux. powerAC/DC85~265V
 ApplicableforDIN-IEC688
 RatingcurrentAC1A, range: AC0~1.5A
 RatingvoltageAC110V, range: AC55~150V
 RatingvoltageAC220V, range: AC160~300V
 InsulationAC2KV/ Min, input/output/power/case
 ABShousing, suitforDinrailmountorwallmount; easily installation

SPECIFICATION

 Power Variation:
 Magnetic Field Effection
 Storage Temperature:
 Adjustment:
 Operating Temperature:
 Long Time Stability:
 Rejection Ratio:
 Insulation:
 Input Load:
 
 Input Frequency:
 Input Overload:
 

 Measuring Range:

 Accuracy:
 Power Effection:
 Output Capability:
 Output Protection:
 Surget Test:

 Response Time:
 Output Ripple:
 Self Powered:
 Housing Material:
 Temp. Coefficient:

AC or DC±20%, 50/60Hz
DIN-ICE688≦0.005%
-40℃~75℃20~90% RH (non-condensing)
SPAN & ZERO ± 1 0%
-10℃~65℃20~95% RH (non-condensing)
≦0.2%
≧120db, 50/60Hz
AC 2KV / Min, input/output/power/case
0.3VA/60Hz, Self Powered 3VA/60Hz; 0.1 VA/60Hz at AC150V, Self Powered 2VA at 150V
45~70Hz or 400Hz
Rating is AC5A, over current is 1 5A, 50A1 0set/hour; 400A 0.5sec/hour
Rating is AC110V, over voltage is 500V, 1200V 10sec/hour; Self Powered: 150V AC Max.
Input 5A, range: AC0~7.5A; Input 1 A, range AC0~1 .5A.
Input 1 1 0V, range 55~1 50V; Input 220V, range1 60~300V.
±0.5% RO at 23℃ ±25℃
≦0.01 %V
Current: >500Ωat 20mA, Voltage: DC1 0mA Maximum.
Against Surge, EMI, RFI.
5KV 1 .2x50uS, ANSI C37.90a/1 983.DIN, IEC255-4, IEC 688-1 992
2.5KV-0.25mS/1 MHz IEC 801 -3(Ring WAVE)
≦400mS
0~99% &0.5% P-P or Option
Output 0~XmA, range: 5~1 50%; 85~1 50V, the energy is from V1 voltage
Flame-Proof ABS housing, UL94 CLASS V-O
≦1 00ppm/℃ From 0~60℃; ≦50ppm/23℃ ±3